Breaker Size Calculator

Minimum and next standard breaker size with NEC 210.20 continuous load rule

Advertisement

Load Parameters

Continuous = energized for 3+ consecutive hours · NEC 210.20(A)

Results

Minimum Standard Breaker Size

20A

Base Load

15.0A

Required (×1.25)

18.8A

Min Wire (75°C Cu)

12 AWG Cu

Standard Breaker Sizes — NEC 240.6(A)

15A20A25A30A35A40A45A50A60A70A80A90A100A110A125A150A175A200A225A250A300A350A400A

NEC 210.20(A): Branch circuit rating ≥ non-continuous load + 125% of continuous load

NEC 210.19(A)(1): Conductor ampacity ≥ branch circuit rating for multi-outlet circuits