Commercial Load Calculator
NEC 220 Part III commercial load calculation with demand factors by occupancy type
Advertisement
Building Parameters
Lighting load for Office: 1 W/sqft × 10,000 sqft = 10,000 W
× 180 VA = 9,000 VA
Commercial Load Calculation Results
Recommended Service Size
150A
208V 3-Phase
Total Connected Load
49,000 VA
Total Demand Load
44,500 VA
Minimum Amps
123.5A
NEC 220.44 Demand Factor Breakdown
General lighting + receptacles19,000 VA
First 10,000 VA @ 100%10,000 VA
Over 10,000 VA @ 50%4,500 VA
General demand subtotal14,500 VA
HVAC (at 100%)30,000 VA
Total demand44,500 VA
NEC 220 Part III Reference
220.12General lighting load based on occupancy type (Table 220.12)
220.44Receptacle demand: first 10 kVA @ 100%, remainder @ 50%
220.14(I)Each receptacle outlet at 180 VA for commercial occupancies
220.50Motor loads per Article 430 (largest motor at 125%)