Dwelling Load Calculator
Full NEC 220 residential load calculation with demand factors for permit applications
Advertisement
General Lighting & Receptacle Load (NEC 220.12 / 220.52)
× 3 VA/sqft = 6,000 VA
× 1,500 VA = 3,000 VA
Appliance Loads
Custom Appliances
NEC 220 Demand Calculation Results
Recommended Service Size
150A
120/240V Single Phase
Total Connected Load
35,100 VA
Demand Load (after factors)
30,225 VA
Minimum Service (amps)
125.9A
NEC 220.42 Demand Factor Breakdown
General lighting + small app + laundry10,500 VA
First 3,000 VA @ 100%3,000 VA
3,001 – 120,000 VA @ 35%2,625 VA
General demand subtotal5,625 VA
Appliance loads (at 100%)24,600 VA
Total demand load30,225 VA
NEC Article 220 Reference
220.12General lighting load: 3 VA per square foot for dwelling units
220.52(A)Small appliance circuits: minimum 2 circuits × 1,500 VA each
220.52(B)Laundry circuit: 1,500 VA minimum (1 circuit required)
220.42Demand factors: first 3,000 VA @ 100%, 3,001–120,000 @ 35%, remainder @ 25%
230.79Minimum service: 100A for single-family dwelling