Lighting Calculator

Fixtures needed, total watts, amps, and ASHRAE 90.1 LPD pass/fail for any room type

Advertisement

Room Dimensions

Room Type

IES Target

50 fc

ASHRAE 90.1 Max LPD

0.82 W/sq ft

Fixture & Electrical

Delivered lumen output per fixture

100 lm/W efficacy

Lighting Design Reference

CU (0.65)Coefficient of Utilization โ€” fraction of fixture lumens reaching the work plane; varies with room geometry and surface reflectances
LLF (0.80)Light Loss Factor โ€” accounts for lamp lumen depreciation, dirt accumulation, and ballast/driver losses over service life
FootcandlesIES RP-1 (Office), RP-7 (Industrial/Warehouse), RP-2 (Retail) illuminance recommendations by task and space type
ASHRAE 90.1Energy standard setting maximum LPD limits by space type; compliance required for most commercial construction permits
NEC 210.19Branch circuit conductor sizing; continuous lighting loads must not exceed 80% of circuit breaker rating
NEC 220.14(D)Track lighting load calculated at 150 VA per 2 ft of track regardless of connected fixture count

Professional disclaimer: Lighting designs must comply with IES illuminance recommendations, ASHRAE 90.1, local energy codes, and ADA/egress requirements. Emergency lighting, exit signs, lighting controls, and dimming are not included in this calculation. Consult a licensed electrical engineer or lighting designer for permitted construction documents.