Motor Circuit Calculator

NEC 430 motor FLA, minimum wire size, branch circuit protection, and overload sizing

Advertisement

Motor Parameters

NEC 430 Motor Circuit Sizing

Full Load Amps (NEC Table 430.250)

7.6A

Min Wire Size

125% FLA = 9.5A

12 AWG Cu

Branch Circuit OCPD

Inverse-time breaker (250%)

20A

Overload Protection

125% FLA = 9.5A

9.5A

NEC 430 Reference

430.22(A)Branch circuit conductors ≥ 125% of motor FLA
430.52(C)(1)Inverse-time breaker rating ≤ 250% of FLA (next standard size up, max 400%)
430.32(A)(1)Overload device ≤ 125% FLA (SF ≥ 1.15 motor); ≤ 115% if SF < 1.15 or unlisted
430.6(A)Use NEC Table 430.247–250 FLA values, not nameplate, for circuit sizing