Motor Circuit Calculator
NEC 430 motor FLA, minimum wire size, branch circuit protection, and overload sizing
Advertisement
Motor Parameters
NEC 430 Motor Circuit Sizing
Full Load Amps (NEC Table 430.250)
7.6A
Min Wire Size
125% FLA = 9.5A
12 AWG Cu
Branch Circuit OCPD
Inverse-time breaker (250%)
20A
Overload Protection
125% FLA = 9.5A
≤ 9.5A
NEC 430 Reference
430.22(A)Branch circuit conductors ≥ 125% of motor FLA
430.52(C)(1)Inverse-time breaker rating ≤ 250% of FLA (next standard size up, max 400%)
430.32(A)(1)Overload device ≤ 125% FLA (SF ≥ 1.15 motor); ≤ 115% if SF < 1.15 or unlisted
430.6(A)Use NEC Table 430.247–250 FLA values, not nameplate, for circuit sizing
Advertisement