Residential Load Calculator
NEC 220.82 optional method service sizing for single-family dwellings
Advertisement
General Loads
6,000 VA lighting load (3 VA/sq ft)
Min 2 required ยท 1500 VA each
Fixed Appliances (at 100%)
Min 5000W per NEC 220.54
Full nameplate
0 if none
0 if none
All others combined
HVAC โ Largest Load Applied
NEC 220.82(C): Use the larger of cooling or electric heating load.
3 tons โ 3,600 VA
Larger load applied: A/C 3,600 VA
Service Sizing Results
Minimum Service Size
150A
Calculated minimum: 135.4A at 240V single-phase
General Loads (demand applied)
10,200 VA10,500 VA โ demand factor
Dryer
5,000 VARange
8,000 VAWater Heater
4,500 VADishwasher
1,200 VAHVAC (largest)
3,600 VATotal Demand Load32,500 VA
NEC 220.82 Method Summary
220.123 VA/sq ft for general lighting
220.52(A)1500 VA per small appliance circuit (min 2)
220.52(B)1500 VA for laundry circuit
220.82(B)General loads: first 10,000 VA at 100%, remainder at 40%
220.82(C)Fixed appliances at 100%; HVAC: use largest of heat or cooling
220.54Dryer: nameplate or 5000W minimum, whichever is larger
For dwellings with 240V single-phase service. EV chargers, hot tubs, and pools add at 100%. Consult AHJ for local amendments.