Voltage Drop Calculator
Voltage drop, drop %, and voltage at load end — single and 3-phase
Advertisement
Circuit Parameters
Results
Voltage Drop
6.58%
Voltage Drop
7.902 V
Voltage at Load
112.10 V
✗ Fail — Exceeds 5% — upsize wire or shorten run
Formula Reference
Single-phase: VD = (2 × K × I × L) / CM
Three-phase: VD = (√3 × K × I × L) / CM
K = 12.9 (copper, 75°C)
K = 21.2 (aluminum, 75°C)
I = load current (amps)
L = one-way length (ft)
CM = circular mils
VD% = (VD ÷ V) × 100
NEC recommends <3% for branch circuits, <5% combined feeder + branch.