Wire Gauge Calculator
Minimum wire size per NEC 310.15 ampacity with derating and voltage drop check
Advertisement
Circuit Parameters
THHN/THWN-2 = 90°C · THWN = 75°C · NM-B = 60°C
Results
Minimum Wire Size (NEC Ampacity)
14 AWG
20A derated capacity
Voltage Drop
10.46%
Drop (volts)
12.55V
Voltage at Load
107.4V
✗ Voltage drop exceeds 5% — wire must be upsized
Upsize to 12 AWG → 6.58% drop
NEC 310.15(B)(16) — Copper Ampacity Reference
30°C ambient, not more than 3 current-carrying conductors in raceway
| Gauge | 60°C | 75°C | 90°C |
|---|---|---|---|
| 14 AWG | 15A | 20A | 25A |
| 12 AWG | 20A | 25A | 30A |
| 10 AWG | 30A | 35A | 40A |
| 8 AWG | 40A | 50A | 55A |
| 6 AWG | 55A | 65A | 75A |
| 4 AWG | 70A | 85A | 95A |
| 3 AWG | 85A | 100A | 110A |
| 2 AWG | 95A | 115A | 130A |
| 1 AWG | 110A | 130A | 150A |
| 1/0 AWG | 125A | 150A | 170A |
| 2/0 AWG | 145A | 175A | 195A |
| 3/0 AWG | 165A | 200A | 225A |
| 4/0 AWG | 195A | 230A | 260A |
| 250 kcmil | 215A | 255A | 290A |
| 300 kcmil | 240A | 285A | 320A |
| 350 kcmil | 260A | 310A | 350A |
| 400 kcmil | 280A | 335A | 380A |
| 500 kcmil | 320A | 380A | 430A |
Conduit derating: 4–6 conductors = 80% · 7–9 = 70% · 10–20 = 50% · 21–30 = 45% · 31–40 = 40%
NEC 210.19(A): Conductor ampacity ≥ non-continuous load + 125% of continuous load
VD formula: VD = (2 × K × I × L) / CM, where K = 12.9 Cu · 21.2 Al