Wire Gauge Calculator

Minimum wire size per NEC 310.15 ampacity with derating and voltage drop check

Advertisement

Circuit Parameters

THHN/THWN-2 = 90°C · THWN = 75°C · NM-B = 60°C

Results

Minimum Wire Size (NEC Ampacity)

14 AWG

20A derated capacity

Voltage Drop

10.46%

Drop (volts)

12.55V

Voltage at Load

107.4V

✗ Voltage drop exceeds 5% — wire must be upsized

Upsize to 12 AWG6.58% drop

NEC 310.15(B)(16) — Copper Ampacity Reference

30°C ambient, not more than 3 current-carrying conductors in raceway

Gauge60°C75°C90°C
14 AWG15A20A25A
12 AWG20A25A30A
10 AWG30A35A40A
8 AWG40A50A55A
6 AWG55A65A75A
4 AWG70A85A95A
3 AWG85A100A110A
2 AWG95A115A130A
1 AWG110A130A150A
1/0 AWG125A150A170A
2/0 AWG145A175A195A
3/0 AWG165A200A225A
4/0 AWG195A230A260A
250 kcmil215A255A290A
300 kcmil240A285A320A
350 kcmil260A310A350A
400 kcmil280A335A380A
500 kcmil320A380A430A

Conduit derating: 4–6 conductors = 80% · 7–9 = 70% · 10–20 = 50% · 21–30 = 45% · 31–40 = 40%

NEC 210.19(A): Conductor ampacity ≥ non-continuous load + 125% of continuous load

VD formula: VD = (2 × K × I × L) / CM, where K = 12.9 Cu · 21.2 Al